Founding master
Adnan Şemiye18 years in the field
MYK-certified master
Adnan Şemiye reads this job in the field. The price is written before work starts.
Tuzla district
Orhanlı 24/7 emergency electrician. In this Tuzla neighbourhood we respond without a minute promise to midnight breaker tripping, residual current device faults, burnt sockets and consumer unit failures. In apartment and complex stock, saturated kitchen circuits, bathroom water heater runs and riser overheating are measured on site. Certified technicians, faults proven with a True-RMS clamp meter and a megohmmeter, written price approval and an official 1 year workmanship guarantee.


Founding master
Adnan Şemiye18 years in the field
MYK-certified master
Adnan Şemiye reads this job in the field. The price is written before work starts.
From the field
Emergency van · +90 582 403 10 87
Orhanlı sits on Tuzla's organised industrial and logistics spine, and most calls here come from a plant board rather than a home. In a facility with a stopped production line the first thing checked is the thermal setting of the motor protection breaker: if it is not matched to the nameplate current the motor exceeds the threshold even at normal load and the breaker opens mid-shift. The nameplate current is read, the actual running current measured with a clamp meter and the thermal recalibrated accordingly.
Contactor tips scorched by heavy inrush raise contact resistance and produce the same outcome, so the contact faces are inspected at every service. The supply is secured with a lockout/tagout kit and the key stays solely with the technician doing the work. Because an outage during a running shift means stopped production, which circuit may be isolated and for how long is confirmed in writing with the plant's technical officer, and the board is handed over after a thermal sweep under load.

In the older stock of Orhanlı a ceramic screw-in fuse board still sits in the hall cupboard. These boards contain no residual current device at all, so protection against electric shock is zero; the fuse melts and welds into its base under overload, fails to clear a short circuit and the body carbonises over time. The sockets usually have no earth either, with the neutral pin bridged to the earth terminal.
The old board is removed entirely and a flame-retardant modular DIN-rail enclosure installed: an independent Type C breaker per room, dedicated circuits for kitchen and bathroom, and a 30 mA Type A residual current device plus a Type 2 surge arrester at the intake. Flat sub-boards use a minimum 6kA breaking capacity and building intakes 10kA. Where a Orhanlı address has no earth, a solid copper electrode is driven, its resistance measured with a digital earth tester and the socket jumpers removed one by one.
If a concealed run in Orhanlı breaks or starts leaking, there is no need to chase the wall end to end. The fault is first narrowed branch by branch at the board, then the route is followed from the surface with an inductive cable tracer and a FLIR thermal imager. A terminal heating under load shows as a clear hot spot on the thermal image and the area to be opened drops to centimetre scale.
Where the leakage is in an under-screed or underground run, a cable fault locator usually narrows the point to within a metre and only that area is opened. If the existing conduit is sound the cable is renewed along the same route with a draw wire; if the conduit is crushed, fire-retardant surface trunking is used. Where breaking is unavoidable its extent and cost are reported in writing first, and nothing is cut at a Orhanlı address without approval.
Istanbul 24/7. Approved certified technician network. Arrival depends on the TEM queue. No fixed minute. TEM is the first queue here.
No. First the high-bay–office split, the label and the clamp are read. Upsizing the ampere hides a hot lug. An office 16 A is not a high-bay branch.
No. The truck dock and the outdoor luminaire stay NYY. NYM is a dry indoor ceiling cable. NHXMH does not drop onto a dock wall.
We have no fixed shop; ElektrikçiGO is a mobile, service-area team working on site across Tuzla. The call lands on the phone, an appointment is set and the technician comes to your address. When they depart, their name, vehicle plate and a live tracking link are shared so you know in advance who is at your door. The survey is done on site and the binding figure written after measurement.
Yes. Parts fitted carry the manufacturer's warranty and the workmanship an official 1 year ElektrikçiGO guarantee. On completion the brand and model of switchgear used, the measured insulation and earth resistance values and the trip time of the 30 mA device are written onto a signed service report and handed to the customer. A copy is kept on file so values can be compared at the next inspection.
Orhanlı, Tuzla. The map is centered on the neighborhood. Arrival changes with the hour and the traffic.